RST_FACTORY
5
4
Writing True (1) to this coil will force
all settings to Factory defaults.
Always read as False (0). After setting
this coil to true, the device will
automatically reset so the new
settings will take effect.
Example MODBUS Request: Read GWC
MODBUS Command: read coils 1-5 (OR RAW 0-4)
DEFAULT MODBUS SETTINGS: Address: 95 (0x5F)
MODBUS ASCII
Poll Gateway Coils: “:63010000000595<CR><LF>“
MODBUS RTU
Poll Gateway Coils: 0x63 01 00 00 00 05 75 8A
• 63 is address
• 01 is function code (read coils)
• 00 is address high
• 00 is address low
• 00 is coil count high
• 05 is coil count low
• 758A is CRC for RTU protocols
95<CR><LF> is the check sum and end-of-line for ASCII protocols