Monnit Serial MODBUS Guide de l'utilisateur Page 17

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 36
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 16
- 17 -
The purpose of these registers is to allow for efficient
access to the remote wireless device’s most current data.
When new data is available from any Wireless device the
FRR is updated with the newly reported values. The FRR
will zero itself out if
no new
data is received within a
defined period. The defined period is specified in the
Wireless Device Registers offset 18.
Any write to the first address in the FRR will zero out the
latest measurement and age. These records consist of
seven (7) registers per wireless device. The format of
these records are: AGE, DATA_0, DATA_1, DATA_2,
DATA_3, BATTERY, RSSI.
Fnct. Code ADDRESS = 41001+ (7 * SLOT)
Raw ADDRESS FORMULA = 1000+(7 * SLOT)
Please see Ref.5 for more information on these registers.
4.11 Viewing Wireless Device Data
(Advanced method)
For a user to see more data about a devices exception and
activity status, the ACTIVE coil @ WDC[SLOT] offset
0 and EXCEPTION coil @ WDC[SLOT] offset 1 can be
queried.
WDC F.C. FORMULA=2001+(4*SLOT)+OFFSET
WDC RAW ADDR FORMULA=2000+(4*SLOT)+OFFSET
Please see Ref.2 for more information on these coils.
For a user to see the detailed data from a device, read
register WDR [SLOT] offset 5 - 15. This will return device
battery voltage, signal strength, and specific status and
data from the device.
WDRF.C.FORMULA=42001*(50* SLOT) + OFFSET
WDR RAW ADDR FORMULA=2000*(50 * SLOT) +
OFFSET
Please see Ref.6 for more details on these registers.